1 / 1 ONLINE UPS

1 / 1 ONLINE UPS
3 KVA - 10 KVA

  • Advanced DSP Technology for stable operation
  • Intelligent Battery Managemen
  • Excellent load characteristics
  • many kinds of system protection and alarming function
  • Personalized Settings For Parameters

Brochure User Manual Enquiry

Features

  • Digital circuit with high speed microprocessor MCU control.
  • Have parameter setting through programmable logic device.
  • Self-test and self-detective analysis. 
  •  Excellent load characteristics: It is completely satisfy to load from 0 to 100% load variation without switch to bypass, which to protect the output more stable and reliable.
  • many kinds of system protection and alarming function: With the input/output over voltage and under voltage protection, input surge protection, battery overcharge and over discharge protection, output overloading, short circuit protection, high temperature protection.
  • High-powered dynamic characteristics: Adopt immediate control mode and effective value kind of feedback control, realized the high dynamic adjustment, reduce the output voltage degree of distortion.
  •  Personalized Settings: It can be setting the UPS working status on the LCD according to the user demand side management. User can optional switch to UPS working mode and EPS working mode.

Applications

  • Major Power Back up source in corporate offices as well as call centres.
  • Banks & ATMs.
  • Defence & Para Military operations complex.
  • Life saving medical equipments and diagnostic labs.
  • Photography and colour labs.Emergency Devices (Lights/Alarms)
  • Fire Devices.
  • Telecommunication Devices.
  • Industrial Applications.
  • Vital real time & process control equipment in industries.
  • Aviation and broadcasting.

Specification

CAPACITY  
KVA 3 kVA 5.1 kVA 7.5 kva 10 kVA
WATT 2.4 kW 4 kW 5.8 kw 8 kW
TYPE Low Freuqency  Transformer Based True On Line-Double Conversion
IN PUT  
Phase Single Phase
Input Power Factor ≧ 0.85 
Input Voltage Range 230VAC  ± 25 % 
Input Frequency Range 50Hz ± 10 %
Output Ripple < 5 %
Soft Start 0~100 % 5 sec
OUT PUT  
Nominal Voltage 220VAC (230VAC or 240VAC), 1P + N  
Output Voltage Regulation ±1 % ( linear load), ± 3% ( Non Linear load)
Output Frequency Range 50Hz ± 0.5%
Crest Factor > 3:1
Output Total Harmonic Pure Sine Wave, 
Distortion (THD) Linear Load < 3%, Non-Linear Load<5%
Dynamic Characteristics Instant voltage<±5% ( from 0 to100% ), Instant recover time<10ms
Overload Capacity At 115% load, normal work, At 125% load 10 min, At 150% load 1min, At 200% load 1S
Inverter Efficiency >92% ( full load )
BATTERY  
Nominal  DC Voltage 96 Vdc 180 Vdc 180 Vdc 180 Vdc
Float Charging Voltage 110 Vdc 207 Vdc 207 Vdc 207 Vdc
Equalized Charging Voltage 112 Vdc 212 Vdc 212 Vdc 212 Vdc
Temp. Compensated Voltage -3mV/℃/cell
Charging Current 2-10 Amp  Setable
Low Voltage Alarm 84.0  ± 0.6 Vdc 158.0  ± 0.6 Vdc 158.0 Vdc ± 0.6 Vdc 158.0 Vdc ± 0.6 Vdc
Low Voltage Trip 80.0  ± 0.6 Vdc  150.0  ± 0.6 Vdc  150.0 vdc ± 0.6 Vdc  150.0 vdc ± 0.6 Vdc 
High Voltage Trip 116.0  ± 0.6 Vdc  218.0  ± 0.6 Vdc  218.0 vdc ± 0.6 Vdc  218.0 vdc ± 0.6 Vdc 
BY PASS  
Phase Single Phase ( P+N )
Manual Maintenance by pass switch provided
Static  No break
PROTECTION   
Input Protection Input voltage, frequency under, over limit protection
Output Protection Over current, short circuit, over voltage, low voltage
Battery Protection Over charge, over-discharge protection
Temperature Protection  inverter over temperature protection
GENERAL PARAMETERS  
Working Environment Temp: -10~40ºC,  relative humidity: 30%~90%
Cooling Method COMPULSIVE VENTILATION
Communitation Interface RS232/ RS485, optional dry contact, SNMP card ( for remote control via internet )
Parallel Operation Hot stand by
Protection Level IP21
Safety Performance V in-n,  V out-n 2000Vac, creepage<10mA , insulating resistance >2 MΩ  (500VDC)
Noise (dB) 50 - 55 55 - 60
Dimension W X H X D  (MM) 345  X  565  X  610 390  X  680  X  680
Weight (Kg) 55 66 91 100